ELECTRICITY METERS
three-phase, active/reactive, multi-functional |
|
Mercury 233 ÀRT
Multi-functional electric energy meter Mercury 233
is designed to register active and reactive electric energy in one direction or two in three-phase
3 or 4-wired network by means of measurement transformers or directly with availability of tariff
registration by day zones, long-term storage and accumulated data transmission through digital
interface wire or wireless communication channels to data collection centers.
Meters may operate both in stand-alone mode and in the structure of
any information measurement system of technical and commercial registration.
Among distinctive features of this meter model is two replaceable
modules for maximum flexibility to construct data collection networks and availability of built-in load
shed relay.
Functions:
- Measurement, registration, storage, output to LCD display and transmission through
interfaces data as follows:
registered active and reactive energy separately
under each tariff and by all tariff sum for the periods as follows:
- total from reset;
- for the current day and by the beginning of the day;
- for the last day and by the beginning of the day;
- for the current month and by the beginning of the month;
- for each of the 11 previous months and by the beginning of each month;
- for the current year and by the beginning of the year;
- for the previous year and by the beginning of the year.
- Meter tariff rater ensures separate tariff schedule for each day of the week taking into account excluded from registration days under 4 tariffs in 16 time zones of the day. Each month of the year is programmed according to individual tariff schedule. Minimum tariff interval within 24 hours makes 1 min.
- Straight direction active energy registration is available separate in each mains phase.
- Registration of technical loss in power lines and supply transformers is also available.
- Additionally, meter ensure registration power mains parameters as follows:
- instantaneous values of active, reactive and total power under each phase and sum by phases with total power vector indication;
- actual values of phase current, voltage, phase voltage angles;
- power factors under each phase and sum by phases;
- sinusoidality phase curve distortion factor.
- Two-channel archive storage of active and reactive energy average power and technical loss power profile with unspecified averaging time of 1-45min. When selecting 30-minute power edges, archive overflow time shall make 85 days.
- Active and reactive power morning and evening peaks fixing at the specified interval with monthly schedule.
- Event log (ringed, 10 records per each event) to fix:
- meter switching on/off time;
- 1,2,3 phase loss/occurence time;
- meter opening/closing time;
- tariff schedule correction time;
- specified power surpassing time…
22 various events in total
- Power quality analyzer function (PQA) with recording voltage and frequency loss/reset time beyond normal and peak values in PQA log (100 records per each event);
- Load control and management function by means of built-in or external disconnection relay. If the preset active power or energy limits are exceeded, meter disconnect user by itself or control user external devices for load shed (for example, emergency circuit breaker).
|
| Technical Features |
- Accuracy class 0.2S, 0.5S, 1.0
- Replaceable interface modules: RS-485, GSM, Bluetooth, PLC, RF, Ethernet, ZigBee;
- Built-in interface – optical port;
- Availability to connect back-up supply Ubackup = 5,5...16V;
- Power, current, voltage, frequency, cosfi measurement;
- 4 standard galvanically isolated telemetry outputs, one per each energy kind;
- 1 load management output;
- Meters operate towards values increase in case of any current circuits phasing connection failure (by module summing);
- Automated self-diagnosis with error display;
- Load management by means of built-in relay or external commutation circuits;
- Electronic seal;
- LCD backlight.

|
| Documents |
|
| |
Data displayed on LCD: |
- active and reactive electric energy consumption under each tariff (up to 4) and sum by all tariffs with accrued total with accuracy up to hundredth of kW*h or kVar*h;
- phase voltage and current in each phase;
- measured value of active, reactive and total power (integration time - 1,28s) both under each phase and sum by three phases with indication of quadrant with total power vector location;
- active and reactive power morning and evening peaks in the current and previous months;
- power factor per each phase and sum by three phases;
- phase voltages angles;
- mains frequency;
- phase curves nonsinusoidality ratio;
- current date and time;
- power mains modem parameters;
- PLC modem signal level pictogram.
|
By means of external PC through «CAN» (or «RS-485» or «IrDA») interface meters ensure reading data and parameters as follows: |
| Parameters |
Pro-
gram-
ming |
Reading |
| •registered active and reactive energy of straight and reverse direction under each of 4 tariffs and sum by tariffs:
- total from reset;
- for the current day;
- by the beginning of the current day;
- for the previous day;
- by the beginning of the previous day;
- for the current month;
- by the beginning of the current month;
- for each of the 11 previous months;
- by the beginning of each of the 11 previous months;
- for the current year;
- by the beginning of the current year;
- for the previous year;
- by the beginning of the previous year.
|
|
+ |
| |
| • interface exchange parameters (disabled for IR port) |
| - current date and time; |
+ |
|
| - even parity / odd parity control; |
+ |
|
| - system time-out duration multiplicator; |
+ |
|
| |
| • password change of data access level 1 (consumer) and 2 (seller); |
+ |
|
| |
| • built-in meter clock parameters: |
| - current date and time; |
+ |
+ |
| - season feature ( winter / summer ); |
+ |
+ |
| - seasonal time automatic transition enable/disable; |
+ |
+ |
| - transition time to summer and winter time provided with the set seasonal time automatic transition; |
+ |
+ |
| |
| • tariff rater parameters : |
| - tariff rater mode (one-tariff/multi-tariff); |
+ |
+ |
| - actual tariff number; |
|
+ |
| - tariff schedule (up to 4 tariffs separately per each day of the week and holidays of each month). Up to 16 tariff intervals per day with setting step not less than1 min); |
+ |
+ |
| - holidays schedule; |
+ |
+ |
| |
| • power profile storage parameters: |
| - integration period duration ; |
+ |
+ |
| - parameters of power profile storage last record in memory; |
|
+ |
| - incomplete edge feature during integration period meter has switched on and off); |
|
+ |
| - memory zeroing enable/disable during average power array memory initialization; |
+ |
+ |
| - feature of average power array memory overflow; |
|
+ |
| - straight direction active and reactive power average values during the specified integration period for load diagram construction in normal and accelerated reading modes; |
|
+ |
| |
| • accessory parameters: |
| - instantaneous values (integration time of 1s) of active, reactive and total power under each phase sum by phases; with direction indication (total power vector position); |
|
+ |
| - actual phase voltage and current values under each phase ; |
|
+ |
| - power factors under each phase and sum by phases with direction indication (total power vector position); |
|
+ |
| - phase voltages angles ; |
|
+ |
| - mains frequency; |
|
+ |
| |
| • individual meter parameters: |
| - network address; |
+ |
+ |
| - serial number; |
|
+ |
| - manufacturing date; |
|
+ |
| - meter positioning; |
+ |
+ |
| - active energy accuracy class ; |
|
+ |
| - reactive energy accuracy class ; |
|
+ |
| - phase summing feature (considering the sign/by module); |
|
+ |
| - meter design (one-directional /cross-current); |
|
+ |
| - rated voltage; |
|
+ |
| - rated current; |
|
+ |
| - voltage transformation ratio; |
+ |
+ |
| - current transformation ratio; |
+ |
+ |
| - meter constant in main mode; |
|
+ |
| - operation temperature range; |
|
+ |
| - pulse output mode (main/verification); |
+ |
+ |
| - SW version; |
|
+ |
| |
| • display modes
: |
| - display period (1..255 s ); |
+ |
+ |
| - display duration of power consumption values under actual tariff (5..255s) in automated operation; |
+ |
+ |
| - display duration of power consumption values under non-actual tariff (5…255s) in automated operation; |
+ |
+ |
| - time-out duration (5…255s) while returning form manual into automated operation; |
+ |
+ |
| - a list of power consumption displayed values (by tariffs sum, tariff1, tariff 2, tariff 3, tariff 4) separately for active and reactive energy in automated parameter change mode; |
+ |
+ |
| - a list of power consumption displayed values (by tariffs sum, tariff1, tariff 2, tariff 3, tariff 4) separately for active and reactive energy in manual parameter change mode; |
+ |
+ |
| |
| • control parameters for straight direction active power and energy specified limits surpassing:
: |
| - control mode ( enable / disable ) for straight direction active power specified limit surpassing ; |
+ |
+ |
| - control mode (enable/disable) for straight direction active energy specified limit surpassing; |
+ |
+ |
| - power specified limit values ; |
+ |
+ |
| - energy specified limit values separately for each of four tariffs; |
+ |
+ |
| - pulse output mode (output 21, 26) (telemetry/load shed unit control mode); |
+ |
+ |
| - load shed unit control mode (load on/off); |
+ |
+ |
| |
| • event log (ringed per 10 events):
- meter switching on/off time;
- time before and after current time correction;
- phase 1, 2, 3 switching on/off time;
- starting/ending time of straight direction active energy limit surpassing (with enabled control);
- correction time of tariff schedule;
- correction time of holiday schedule;
- reset time of accumulated energy registers;
- initialization time of average power array;
- surpassing time of straight direction active energy limits under each tariff (with enabled control);
- correction time of power limits surpassing control parameters;
- correction time of energy limits surpassing control parameters;
- correction time of technical loss registration parameters;
- meter opening/closing time;
|
|
+ |
| |
| • Power quality analyzer function (PQA) log (ringed per 100 records): |
|
+ |
| • Meter self-diagnosis word status |
|
+ |
| Main Technical Specifications |
| Characteristics |
values |
Accuracy class (active / reactive)
-
transformer connection
-
direct connection |
0,2S/0.5; 0,5S/1,0
1,0/ 2,0
|
Rated voltage , V
-
transformer connection
-
direct connection |
3*57,7/100
3*230/400
|
Rated (maximum) current, A
-
transformer connection
-
direct connection |
5(10)
5(60); 10(100)
|
Maximum current for transformer connection meters within 0,5s, À |
200 |
Maximum current for direct connection meters
within 10ms, À
- for I base =5 À
- for I base =10 À
|
1800
3000 |
| Starting current (sensitivity), À
for ART-00 (Unom 57,7 V, I nom 5 A)
for ART-01 (Unom 220 V, I nom 5 A)
for ART-02 (Unom 220 V, I nom 10 A)
for ART-03 (Unom 220 V, I nom 5 A) |
0,005
0,020
0,040
0,005 |
Active/total power consumption by each parallel meter circuit, W/V À not over
- for U nom =57,7
- for U nom =230 |
1,0 / 2,0
1,0 / 8,0 |
| Extra total power consumption of the meter with installed interface modem, V À , not over |
2,5 |
| Average current consumption from external GSM modem power supply during transmission , A , not over |
1,0 |
External back - up supply voltage , V
|
5,5....16
|
Total power consumed by current circuit, V* À , not over
|
0,1
|
Tariffs
|
4
|
| Tariff seasons ( months ) |
12 |
| Clock accuracy at t=20± 5 °C , s/day |
± 0,5 |
Galvanically isolated pulse outputs:
- telemetry
- load management |
4 (1 programmed )
1 |
| Transmission ratio of basic/verification output, imp/kW, imp/kVAr:
for ART-00 (Unom 57,7 V, I nom 5 A)
for ART-01 (Unom 220 V, I nom 5 A)
for ART-02 (Unom 220 V, I nom 10 A)
for ART-03 (Unom 220 V, I nom 5 A) |
5000/160000
1000/32000
500/16000
1000/160000 |
| Tariff seasons ( months ) |
12 |
| Tariff seasons ( months ) |
12 |
| Transmission ratio of basic/verification output, imp/kW, imp/kVAr:
for ART-00 (Unom 57,7 V, I nom 5 A)
for ART-01 (Unom 220 V, I nom 5 A)
for ART-02 (Unom 220 V, I nom 10 A)
for ART-03 (Unom 220 V, I nom 5 A) |
5000/160000
1000/32000
500/16000
1000/160000 |
Data safety in case of power supply failure, years
- constant data
- operative data |
40
10 |
| Data protection |
two access levels and hardware protection of metrological coefficients memory |
| Built-in digital interfaces |
Optical port |
| modules |
BlueThooth, RF(RF modem), Ethernet, ZigBee |
| Exchange speed, bit/s:
- through interface CAN and RS-485;
- through infrared port;
|
300, 600, 1200, 2400, 4800, 9600
9600
|
| Meter self-diagnosis |
Available |
| Housing protection rate |
IP54 |
| Temperature range, °Ñ |
from -40 to +55 |
| Calibration period, years |
10 |
| Interval between verifications, years |
10 |
| Weight, kg |
not over 1,8 |
| Dimensions (length, width, height), mm |
295*170*80 |
| Mean time between failures, hours |
120000 |
| Service life, years, not less |
30 |
| Warranty period, years |
3 |
|
|
Mercury 233ART2-0X O K R(G,B,F,E,Z) R(L,B,F,E,Z)
Mercury –
meter trade name
233 -
meter series
A -
active energy measurement
R -
reactive energy measurement
T -
inner tariff rater availability
2 -
two registration directions
0X –
modifications subdivided by current, voltage and accuracy class.
|
0X |
Rated voltage , V |
Rated (base) current, A |
Maximum current, À
|
Accuracy class at measurement of
|
| Active energy |
Reactive energy |
|
00 |
3*57,7(100) |
5 |
10 |
0,2S; 0,5S |
0,5; 1,0 |
|
01 |
3*230(400) |
5 |
60 |
1,0 |
2,0 |
|
02 |
3*230(400) |
10 |
100 |
1,0 |
2,0 |
|
03 |
3*230(400) |
5 |
10 |
0,2S; 0,5S |
0,5; 1,0 |
Î Ê-
load management, in particular:
Î -
through meter inner relay;
Ê -
through external disconnection management unit output;
R (G,B,F,E,Z) - èíòåðôåéñ ¹1, à èìåííî:
R -
RS485 interface
G -
GSM modem
B - BlueTooth
F -
RF (RF interface)
E - Ethernet
Z - ZigBee
R (L,B,F,E,Z) -
interface ¹2, in particular:
R -
RS485 interface
L -
PLC modem
B - BlueTooth
F -
RF (RF interface)
E - Ethernet
Z - ZigBee
Missing symbol in meter denomination stands for the relevant function unavailability. . |

|