ENERGY METERS
Three-phase, active/reactive, multifunctionalå |
|
Mercury 230 ÀRT
Meters are designed for registration
of active and reactive energy in one direction in 3- or 4-wire networks of
alternating current and operate either autonomous or within AMR.
Basic functions:
- Measurement, registration, storage, output to LCD monitor and transmission through interfaces IrDA, CAN, RS-485 of the following data:
- quantity of registered active and reactive energy separately by each tariff and total of all tariffs
- total from indications reset
- for current day and for the beginning of a day
- for previous day and for the beginning of a day
- for current month and for beginning of a month
- for each of 11 previous months and for the beginning of month
- for current year and for beginning of a year
- for previous year and for beginning of a year
- Tarifficator of meter provides possibility of registration by 4 tariffs in 16 timing zones of a day for 4 types of days. Each month of a year is programmed with individual timetable. Minimum tariff working interval within a day – 1 minute
- Possibility of straight direction active energy registration separately in each network phase by each tariff with growing total and by tariffs total with data transmission through wire interfaces.
- Possibility of registering technical losses in power lines and transformers;
- Additionally meter provides output to LCD indicator and transmission through wire interfaces of the following network values:
- instantaneous values of active, reactive and full power by each phase and by phases total with
indication full power vector direction
- functioning values of phase currents, voltages, angles between network frequency phase voltages
- network frequency
- power factors by each phase and by phases total
- Input of active power and energy limits and programmable control of external consumer switch off load devices in case limits are exceeded.
- Transmission of measuring and registration results through interfaces CAN, RS-485, IrDA
- Meters programming in the mode of phases summation “on module” to prevent energy theft if meter current circuits connection phasing is wrong.
|
| Technical specifications |
- Accuracy class 0.5s, 1.0s
- interfaces: CAN, RS-485, IrDA,
- measuring power, currents, voltages, cos F
- PLC modem can be embedded for data transmission on power line 220V (depending on modification)
- two standard galvanic unbound telemetric outputs (DIN 43864), one for each energy type;
- meters operate towards values increase in case of any wrong phasing of current circuits
- load control through external circuits of commutation
- electronic seal
|
| Documents |
|
|
Additional functions (depending on modification):
- Storage of two-channel archive of average power values of active and reactive energy and technical losses power profile with voluntary integration time from 1 to 45 minutes with step 1 minute. With 30-minutes duration of integration the archives overflow time is 85 days.
- Storage of two-channel archive of average power values of active and reactive energy and technical losses power profile with voluntary integration time from 1 to 45 minutes with step 1 minute. With 30-minutes duration of integration the archives overflow time is 85 days.
- meter on/off time
- phases 1,2,3 on/off time
- devices opening/closing time;
- tariff timetable correction time
- time of exceeding set energy and power limits
total over 15 different events - Connection of external backup power supply for reading or measuring data and reading data in case of meter power failure
|
Meters indicate on LCD display: |
- Consumed active and reactive energy value for each tariff (up to four) and total for all tariffs with growing total and accuracy up to hundredth parts of kWh and kVAh;
- Phase voltage and current in each phase;
- Measured value of active, reactive and full power (integration time 1 s) both for each phase and total for three phases with indication of quadrant, in which there is a full power vector;
- Power factor for each phase and total for three phases;
- Angles between phase voltages;
- Network frequency;
- Current date and time
- Power line modem values
- Modem signal level sign
|
Meters provide reading by external PC through interfaces «CAN» , «IrDA» or RS-485 of the following values and data:
|
| Parameters |
Programming |
Reading |
• interface exchange parameters (prohibited for infrared port) |
- exchange speed; |
+ |
|
- evenness/unevenness control; |
+ |
|
- system time-out duration multiplier; |
+ |
|
| • registered active and reactive energy of direct and reverse direction for each of 4 tariffs and total for tariffs;
- total from indications reset;
- for current date;
- for the beginning of current date;
- for previous date;
- for the beginning of previous date;
- for current month;
- for the beginning of current month;
- for each of previous 11 months;
- for the beginning of each of previous 11 months;
- for current year;
- for the beginning of current year;
- for last year;
- for the beginning of last year
| |
+ |
• meter internal clock values: |
- current date and time; |
+ |
+ |
- season time sign (winter/summer); |
+ |
+ |
- permission/prohibition of automatic switch of season time; |
+ |
+ |
- time of switching to “summer” and “winter” time and automatic set of seasonal time; |
+ |
+ |
• tarifficator values: |
- tarifficator modes (one-tariff/multi-tariff); |
+ |
+ |
- current tariff number; |
|
+ |
- tariff timetable (up to 4 tariffs separately for each day of week and holidats of each month. Up to 16 tariff intervals in a day with set up step not less 1 min); |
+ |
+ |
- holidays calendar; |
+ |
+ |
• powers profile saving values: |
- integration time duration; |
+ |
+ |
- last record values in powers profile storage memory; |
|
+ |
- incomplete cut signs (counter switched on or off during integration); |
|
+ |
- permission/restriction of memory zeroing during initializing of average voltages array memory; |
+ |
+ |
- average powers array memory overflow sign; |
|
+ |
- average values of active and reactive powers of straight direction for given integration period for making load diagrams in basic and speeded up reading modes; |
|
+ |
• auxiliary values: |
- instantaneous values (with integration time 1 s) of active, reactive and full power on each phase and on phases total; with indication of direction (full power vector position); |
|
+ |
- functioning values of phase voltages and currents on each phase; |
|
+ |
- power factors on each phase and on phases total with indication of direction (full power vector position); |
|
+ |
- angles between phase voltages; |
|
+ |
- network frequency; |
|
+ |
•meters individual values: |
- network address; |
+ |
+ |
- serial number; |
|
+ |
- manufacturing date; |
|
+ |
- meter position; |
+ |
+ |
- accuracy class on active energy; |
|
+ |
- accuracy class on reactive energy; |
|
+ |
- phases summation sign (taking into account sign/ by module); |
|
+ |
- meter performance version (one-directional/overflowing); |
|
+ |
- nominal voltage; |
|
+ |
- nominal current; |
|
+ |
- transformation coefficient by voltage; |
+ |
+ |
- transformation coefficient by current; |
+ |
+ |
- meter constant in basic mode; |
|
+ |
- operation temperature range; |
|
+ |
- impulse output modes (basic/verification); |
+ |
+ |
- software version; |
|
+ |
• indication modes: |
- indication period (1..255 seconds); |
+ |
+ |
- consumed energy indications displaying duration on current tariff (5..255 seconds) in automatic mode; |
+ |
+ |
- consumed energy indications displaying duration on non-current tariff (5..255 seconds) in automatic mode; |
+ |
+ |
- time-out duration (5…255 seconds) during switching from manual to automatic mode |
+ |
+ |
- consumed energy displayed indications list (by tariff sum, tariff 1, tariff 2, tariff 3, tariff 4) separately for active and reactive energy in automatic values shifting mode; |
+ |
+ |
- consumed energy displayed indications list (by tariff sum, tariff 1, tariff 2, tariff 3, tariff 4) separately for active and reactive energy in manual values shifting mode; |
+ |
+ |
• straight direction active power and energy set limits exceeding control values: |
-control mode (permission/prohibition) for exceeding straight direction active power set limit; |
+ |
+ |
- control mode (permission/prohibition) for exceeding straight direction active energy set limit; |
+ |
+ |
- set power limit values; |
+ |
+ |
- set energy limit values separately for each of four tariffs; |
+ |
+ |
- impulse output mode (pins 21, 26) (telemetry/load switch off unit control mode); |
+ |
+ |
- load switch off unit control mode (load switched on/off); |
+ |
+ |
| • events journal (circle for 10 records):
- meter on/off time;
- time before/after current time adjustment;
- phases 1,2,3 on/off time
- straight direction active power limit exceeding
beginning/ending time (at permitted control) ;
- tariff timetable adjustment time;
- holidays timetable adjustment time;
- accumulated energy registers reset time;
- average powers array initializing time;
- energy limit exceeding control values adjustment time;
- power limit exceeding control values adjustment time;
- technical losses registration values adjustment time;
- devices opening/closing time; |
|
+ |
| • meter self-diagnostic condition. |
|
+ |
Transmission of the following data about consumed energy with growing total |
- starting from beginning of meter operation on tariff and phases sum in case meter is programmed in one-tariff mode; |
- starting from beginning of meter operation on current tariff and phases sum on the moment of request in case meter is programmed in multi-tariff mode; |
• Receiving of the following data: |
- built-in modem network identifier; |
- command of temporal switch to auxiliary data transmission; |
- current date and time |
| Characteristics |
values |
Accuracy class for
- active energy
- reactive energy |
0,5S or 1,0S
1,0 or 2,0 |
| Nominal voltage, V |
3*57,7/100 or 3*220/380 |
| Nominal (max) current, A |
5(7,5); 5(50); 10(100) |
Maximum current within 0,5 s, À
- for Inom=5À
- for Inom=10À |
150
200 |
Sensitivity for measuring
- active energy, Wò
- reactive energy, VAr |
0,36; 1,38
0,72; 2,75 |
| Active / full consumable power by each meter parallel circuit, W/VA not over |
0,5 / 7,5 |
| Full power, consumed by current circuit, not over V*A |
0,1 |
| Number of tariffs |
4 |
| Number of tariff seasons (months) |
12 |
| Exchange speed, bit/s:
- through interface CAN and RS-485;
- through infrared port;
|
300, 600, 1200, 2400, 4800, 9600
9600
|
| Transmission ratio of basic/verification output, imp/kW, imp/kVAr:
for ART-00 (Unom 57,7 V, I nom 5 A)
for ART-01 (Unom 220 V, I nom 5 A)
for ART-02 (Unom 220 V, I nom 10 A)
for ART-03 (Unom 220 V, I nom 5 A) |
5000/160000
1000/32000
500/16000
1000/160000 |
Data safety in case of power supply failure, years
- constant data
- operative data |
40
10 |
| Data protection |
two access levels and hardware protection of metrological coefficients memory |
| Temperature range, °Ñ |
from -40 to +55 |
| Interval between verifications, years |
10 |
| Mass, kg |
not over 1,5 |
| Dimensions (length, width, height), mm |
258*170*74 |
| Warranty period, years |
3 |
|
|
| Meter designation |
Nominal voltage,
V |
Nominal (max) current, A |
Accuracy class for measuring active/reactive energy |
Communication interface |
Backup power supply connection |
Power profiles
Event journal |
Mercury 230 ART(2)-XX PC(R)IDN of direct and transformer connection |
| ÀÐÒ-00 Ñ(R) |
3*57,7/100 |
5(7,5) |
0,5 / 1,0 |
CAN or RS485 |
- |
- |
| ÀÐÒ-01 Ñ(R) |
3*220/380 |
5(50) |
1,0 /2,0 |
CAN or
RS485 |
- |
- |
| ÀÐÒ-02 Ñ(R) |
3*220/380 |
10(100) |
1,0 / 2,0 |
CAN or
RS485 |
- |
- |
| ÀÐÒ-03 Ñ(R) |
3*220/380 |
5(7,5) |
0,5 / 1,0 |
CAN or
RS485 |
- |
- |
| ÀÐÒ-00 PÑ(R)IDN |
3*57,7/100 |
5(7,5) |
0,5 / 1,0 |
CAN or
RS485),
IrDA |
+ |
+ |
| ÀÐÒ-01 PÑ(R)IN |
3*220/380 |
5(50) |
1,0 /2,0 |
CAN or
RS485,
IrDA |
- |
+ |
| ÀÐÒ-02 PÑ(R)IN |
3*220/380 |
10(100) |
1,0 /2,0 |
CAN or
RS485,
IrDA |
- |
+ |
| ÀÐÒ-03 PÑ(R)IDN |
3*220/380 |
5(7,5) |
0,5 / 1,0 |
CAN or
RS485,
IrDA |
+ |
+ |
Mercury 230 ART(2)-XX CLN of direct and transformer connection with built-in PLC modem |
| ÀÐÒ-01 ÑLN |
3*220/380 |
5(50) |
1,0 /2,0 |
CAN,
PLC-ìîäåì |
- |
- |
| ÀÐÒ-02 ÑLN |
3*220/380 |
10(100) |
1,0 /2,0 |
CAN,
PLC-ìîäåì |
- |
- |
| ÀÐÒ-03 ÑLN |
3*220/380 |
5(7,5) |
0,5 / 1,0 |
CAN,
PLC-ìîäåì |
- |
- |
| In meter designation: |

 |
|