Three-phase, active/reactive, multifunctionalå |

|
Mercury 230 ÀRT2
Meters are designed for registration of active and reactive energy and power in one or two directions in three-phase 3- or 4-wire networks of alternating current with frequency 50 Hz through measuring transformers or directly with possibility of tariff registration and transmission of accumulated data about energy consumption through digital interface channels.
Operated either autonomous or within any information-measuring systems of technical and commercial registration.
Meters provide:
- Measurement, registration, storage, output to LCD monitor and transmission through interfaces IrDA, CAN, RS-485 of the following data:
quantity of registered active and reactive energy separately by each tariff and total of all tariffs
- total from indications reset
- for current day and for the beginning of a day
- for previous day and for the beginning of a day
- for current month and for beginning of a month
- for each of 11 previous months and for the beginning of month
- for current year and for beginning of a year
- for previous year and for beginning of a year
- Possibility of registration by 4 tariffs in 16 timing zones of a day separately for each day of a week and holidays. Each month of a year is programmed with individual timetable. Minimum tariff working interval within a day – 1 minute
- Possibility of straight direction active energy registration separately in each network phase by each tariff with growing total and by tariffs total with data transmission through wire interfaces.
- Technical losses registration in power lines and transformers, forming losses profile;
- Measuring, output to LCD indicator and transmission through wire interfaces of the following network values:
- instantaneous values of active, reactive and full power by each phase and by phases total with
indication full power vector direction
- functioning values of phase currents, voltages, angles between network frequency phase voltages
- network frequency
- power factors by each phase and by phases total
- Storage of four-channel archive of average power values of active and reactive energy of two directions and technical losses power profile with voluntary integration time from 1 to 54 minutes. With 30-minutes duration of integration the archives overflow time is 85 days.
- Registration of morning and evening maximums of active and reactive power in given interval with monthly timetable
- Input of active power and energy limits and programmable control of external consumer switch off load devices in case limits are exceeded.
- Transmission of measuring and registration results through interfaces CAN, RS-485, IrDA
- Meters programming in the mode of phases summation “on module” to prevent energy theft if meter current circuits connection phasing is wrong.
- Connection of external backup power supply for reading or measuring values in case of meter power supply failure
- Meter journals (circle, 10 records for each event) register:
- meter on/off time
- phases 1,2,3 on/off time
- time of phase voltage exceeding/returning back from permitted limits
- devices opening/closing time;
- last programming time
- tariff timetable correction time
- time of exceeding set energy and power limits
total over 15 different events
(journal contains 100 records) |
| Technical specifications |
- - Accuracy class 0.5s, 1.0s
- - interfaces: CAN, RS-485, IrDA
- - network values measuring: P, U, I, cosF;
- - four standard galvanic unbound telemetric outputs (DIN 43864), one for each energy type and registration direction;
- - meters operate towards values increase in case of any wrong phasing of current circuits
- - electronic seal
- - load control through external circuits of commutation
- - self diagnostic with indication of mistakes
- - presence of journals: events, energy quality values, status
- - possibility of power backup connection Ubac = 5,5...9 V
|
| Documents |
|
 |
Meters indicate on LCD display: |
- Consumed active and reactive energy value for each tariff (up to four) and total for all tariffs with growing total and accuracy up to hundredth parts of kWh and kVAh;
- Phase voltage and current in each phase;
- Measured value of active, reactive and full power (integration time 1 s) both for each phase and total for three phases with indication of quadrant, in which there is a full power vector;
- Power factor for each phase and total for three phases;
- Angles between phase voltages;
- Network frequency;
- Current date and time
|
Meters provide reading by external PC through interfaces «CAN» , «IrDA» or RS-485 of the following values and data: |
| Parameters |
Programming |
Reading |
• interface exchange parameters (prohibited for infrared port) |
- exchange speed; |
+ |
|
- evenness/unevenness control; |
+ |
|
- system time-out duration multiplier; |
+ |
|
• registered active and reactive energy of direct and reverse direction for each of 4 tariffs and total for tariffs; |
+ |
|
• registered active and reactive energy of direct and reverse direction for each of 4 tariffs and total for tariffs;
- total from indications reset;
- for current date;- for the beginning of current date;
- for previous date; - for the beginning of previous date;
- for current month;
- for the beginning of current month;
- for each of previous 11 months;
- for the beginning of each of previous 11 months;
- for current year; - for the beginning of current year;
- for last year;- for the beginning of last year
|
|
+ |
| • meter internal clock values: |
- current date and time; |
+ |
+ |
- season time sign (winter/summer); |
+ |
+ |
- permission/prohibition of automatic switch of season time; |
+ |
+ |
- time of switching to “summer” and “winter” time and automatic set of seasonal time; |
+ |
+ |
• tarifficator values: |
- tarifficator modes (one-tariff/multi-tariff); |
+ |
+ |
- current tariff number; |
|
+ |
- tariff timetable (up to 4 tariffs separately for each day of week and holidats of each month. Up to 16 tariff intervals in a day with set up step not less 1 min); |
+ |
+ |
- holidays calendar; |
+ |
+ |
• powers profile saving values: |
- integration time duration; |
+ |
+ |
- last record values in powers profile storage memory; |
|
+ |
- incomplete cut signs (counter switched on or off during integration); |
|
+ |
- permission/restriction of memory zeroing during initializing of average voltages array memory; |
+ |
+ |
- average powers array memory overflow sign; |
|
+ |
- average values of active and reactive powers of straight direction for given integration period for making load diagrams in basic and speeded up reading modes; |
|
+ |
• auxiliary values: |
- instantaneous values (with integration time 1 s) of active, reactive and full power on each phase and on phases total; with indication of direction (full power vector position); |
|
+ |
- functioning values of phase voltages and currents on each phase; |
|
+ |
- power factors on each phase and on phases total with indication of direction (full power vector position); |
|
+ |
- angles between phase voltages; |
|
+ |
- network frequency; |
|
+ |
•meters individual values: |
- network address; |
+ |
+ |
- serial number; |
|
+ |
- manufacturing date; |
|
+ |
- meter position; |
+ |
+ |
- accuracy class on active energy; |
|
+ |
- accuracy class on reactive energy; |
|
+ |
- phases summation sign (taking into account sign/ by module); |
|
+ |
- meter performance version (one-directional/overflowing); |
|
+ |
- nominal voltage; |
|
+ |
- nominal current; |
|
+ |
- transformation coefficient by voltage; |
+ |
+ |
- transformation coefficient by current; |
+ |
+ |
- meter constant in basic mode; |
|
+ |
- operation temperature range; |
|
+ |
- impulse output modes (basic/verification); |
+ |
+ |
- software version; |
|
+ |
• indication modes: |
- indication period (1..255 seconds); |
+ |
+ |
- consumed energy indications displaying duration on current tariff (5..255 seconds) in automatic mode; |
+ |
+ |
- consumed energy indications displaying duration on non-current tariff (5..255 seconds) in automatic mode; |
+ |
+ |
- time-out duration (5…255 seconds) during switching from manual to automatic mode |
+ |
+ |
- consumed energy displayed indications list (by tariff sum, tariff 1, tariff 2, tariff 3, tariff 4) separately for active and reactive energy in automatic values shifting mode; |
+ |
+ |
- consumed energy displayed indications list (by tariff sum, tariff 1, tariff 2, tariff 3, tariff 4) separately for active and reactive energy in manual values shifting mode; |
+ |
+ |
• straight direction active power and energy set limits exceeding control values: |
-control mode (permission/prohibition) for exceeding straight direction active power set limit; |
+ |
+ |
- control mode (permission/prohibition) for exceeding straight direction active energy set limit; |
+ |
+ |
- set power limit values; |
+ |
+ |
- set energy limit values separately for each of four tariffs; |
+ |
+ |
- impulse output mode (pins 21, 26) (telemetry/load switch off unit control mode); |
+ |
+ |
- load switch off unit control mode (load switched on/off); |
+ |
+ |
• events journal (circle for 10 records):
- meter on/off time;
- time before/after current time adjustment;
- phases 1,2,3 on/off time
- straight direction active power limit exceeding beginning/ending time (at permitted control) ;
- tariff timetable adjustment time;
- holidays timetable adjustment time;
- accumulated energy registers reset time;
- average powers array initializing time;
- straight direction active energy limit exceeding beginning/ending time (at permitted control);
- power limit exceeding control values adjustment time;
- energy limit exceeding control values adjustment time;
- technical losses registration values adjustment time;
- devices opening/closing time;
|
|
+ |
| • meter self-diagnostic condition. |
|
+ |
| Characteristics |
values |
Accuracy class for
- active energy
- reactive energy
|
0,5S
1,0 |
| Nominal voltage, V |
3*57,7/100 or 3*220/380 |
| Nominal (max) current, A |
5(7,5) |
Maximum current within 0,5 s, À
- for Inom=5À
|
150 |
Sensitivity for measuring
- active energy, Wò
- reactive energy, VAr |
0,36
0,72 |
| Active / full consumable power by each meter parallel circuit, W/VA not over |
0,5 / 7,5 |
| Full power, consumed by current circuit, not over V*A |
0,1 |
| Number of tariffs |
4 |
| Number of tariff seasons (months) |
12 |
| Exchange speed, bit/s:
- through interface CAN and RS-485;
- through infrared port;
|
300, 600, 1200, 2400, 4800, 9600
9600 |
|
Transmission ratio of basic/verification output, imp/kW, imp/kVAr:
for ART-00 (Unom 57,7 V, I nom 5 A)
for ART-03 (Unom 220 V, I nom 5 A)
|
5000/160000
1000/160000
|
Data safety in case of power supply failure, years
- constant data
- operative data |
40 10 |
| Data protection |
two access levels and hardware protection of metrological coefficients memory |
| Temperature range, °Ñ |
from -40 to +55 |
| Interval between verifications, years |
10 |
| Mass, kg |
not over 1,5 |
| Dimensions (length, width, height), mm |
258*170*74 |
| Warranty period, years |
3 |
|
|
Meter designation
|
Nominal voltage, V |
Nominal (max) current, A |
Accuracy class for measuring active/reactive energy |
Communication interface |
Backup power supply connection |
Power profiles
Event journal |
| Mercury 230 ART(2)-XX PC(R)IDN of transformer connection by current and voltage |
ÀRÒ2-00 PÑ(R)IDN
Bi-directional |
3*57,7/100 |
5(7,5) |
0,5 / 1,0 |
CAN or
(RS485),
IrDA |
+ |
+ |
ÀRÒ2-03 PÑ(R)IDN
Bi-directional |
3*57,7/100 |
5(7,5) |
0,5 / 1,0 |
CAN or
RS485,
IrDA |
+ |
+ |