ENERGY METERS
Three-phase, active/reactive




Mercury 230 ÀR


Meters are designed for registration of active and reactive energy in one direction in 3- or 4-wire networks of alternating current and operate either autonomous or within AMR.

Meters provide:
  • Energy registration by each phase of three-phase network in one- or multi-tariff (switching by interface signals) modes as well total on all phases.
  • Indication on LCD active and reactive energy with growing total from indications reset on each tariff and on tariff sum..
  • Measuring of instantaneous values of active, reactive and full power on each phase ond on phases sum with indication of direction;
  • Measuring by phases: current, voltage, frequency, cos F, angles between phase voltages.
  • Programmable control of external devices of consumer load switching on/off.
  • Transmission of measuring results through power line 220/380V (only consumed energy) and through CAN, RS-485 (all existing data).
  • Meters programming in phases summation mode “by module” to avoid energy theft if meter current circuits connection phasing is wrong.
  • Meter internal clock correction.
Technical specifications
  • Accuracy class 0.5s, 1.0s
  • interfaces: CAN, RS-485
  • measuring network values
  • tariff switching (up to four) is realized with interface signals
Documents
Meters indicate on LCD display:
  • Consumed active and reactive energy value for each tariff (up to four) and total for all tariffs with growing total and accuracy up to hundredth parts of kWh and kVAh;
  • Phase voltage and current in each phase;
  • Measured value of active, reactive and full power (integration time 1 s) both for each phase and total for three phases with indication of quadrant, in which there is a full power vector;
  • Power factor for each phase and total for three phases;
  • Angles between phase voltages;
  • Network frequency;
  • Current date and time
  • Power line modem values
  • Modem signal level sign

Meters provide reading by external PC through interfaces «CAN» , «IrDA» or RS-485 of the following values and data:

Parameters Programming Reading

• interface exchange parameters (prohibited for infrared port)

- exchange speed;

+ +

- evenness/unevenness control;

+ +

- system time-out duration multiplier;

+  

• changing passwords of first (consumer) and second (seller) access level to data

+  
• registered active and reactive energy of direct and reverse direction for each of 4 tariffs and total for tariffs;
- total from indications reset;
- for current date;
- for the beginning of current date;
- for previous date;
- for the beginning of previous date;
- for current month;
- for the beginning of current month;
- for each of previous 11 months;
- for the beginning of each of previous 11 months;
- for current year; - for the beginning of current year;
- for last year;- for the beginning of last year
  +

• auxiliary values:

- instantaneous values (with integration time 1 s) of active, reactive and full power on each phase and on phases total; with indication of direction (full power vector position);

  +

- functioning values of phase voltages and currents on each phase;

  +

- power factors on each phase and on phases total with indication of direction (full power vector position);

  +

- angles between phase voltages;

  +

- network frequency;

  +

•meters individual values:

- network address;

+ +

- serial number;

  +

- manufacturing date;

  +

- meter position;

+ +

- accuracy class on active energy;

  +

- accuracy class on reactive energy;

  +

- phases summation sign (taking into account sign/ by module);- meter performance version (one-directional/overflowing);

+ +

- nominal voltage;

  +

- nominal current;

  +

- transformation coefficient by voltage;

+ +

- transformation coefficient by current;

+ +

- meter constant in basic mode;

  +

- operation temperature range;

  +

- impulse output modes (basic/verification);

+ +

- software version;

  +

• indication modes:

- indication period (1..255 seconds);

+ +

- consumed energy indications displaying duration on current tariff (5..255 seconds) in automatic mode;

+ +

- consumed energy indications displaying duration on non-current tariff (5..255 seconds) in automatic mode;

+ +

- time-out duration (5…255 seconds) during switching from manual to automatic mode

+ +

• straight direction active power and energy set limits exceeding control values:

-control mode (permission/prohibition) for exceeding straight direction active power set limit;

+ +

- control mode (permission/prohibition) for exceeding straight direction active energy set limit;

+ +

- set power limit values;

+ +

- set energy limit values separately for each of four tariffs;

+ +

- impulse output mode (pins 21, 26) (telemetry/load switch off unit control mode);

+ +

- load switch off unit control mode (load switched on/off);

+ +
• meter self-diagnostic condition.   +

PLC interface provide:

Transmission of the following data about consumed energy with growing total

- starting from beginning of meter operation on tariff and phases sum in case meter is programmed in one-tariff mode;

- starting from beginning of meter operation on current tariff and phases sum on the moment of request in case meter is programmed in multi-tariff mode;

• Receiving of the following data:

- built-in modem network identifier;

- command of temporal switch to auxiliary data transmission;

- current date and time


Basic specifications

Characteristics values
Accuracy class for
   - active energy
   - reactive energy

0,5S or 1,0S
1,0 or 2,0
Nominal voltage, V 3*57,7/100 or 3*220/380
Nominal (max) current, A 5(7,5); 5(50); 10(100)
Maximum current within 0,5 s, À
  - for Inom=5À
  - for Inom=10À

150
200
Sensitivity for measuring
   - active energy, Wò
   - reactive energy, VAr

0,36; 1,38
0,72; 2,75
Active / full consumable power by each meter parallel circuit, W/VA not over 0,5 / 7,5
Full power, consumed by current circuit, not over V*A 0,1
Number of tariffs 1 (int), 4(ext)
Exchange speed, bit/s:
- through interface CAN and RS-485;
- through infrared port;

300, 600, 1200, 2400, 4800, 9600
9600
Transmission ratio of basic/verification output, imp/kW, imp/kVAr:
for ART-00 (Unom 57,7 V, I nom 5 A)
for ART-01 (Unom 220 V, I nom 5 A)
for ART-02 (Unom 220 V, I nom 10 A)
for ART-03 (Unom 220 V, I nom 5 A)


5000/160000
1000/32000
500/16000
1000/160000
Data safety in case of power supply failure, years
   - constant data
   - operative data

40
10
Data protection two access levels and hardware protection of metrological coefficients memory
Temperature range, °Ñ from -40 to +55
Interval between verifications, years 10
Mass, kg not over 1,5
Dimensions (length, width, height), mm 258*170*74
Warranty period, years 3

Performance versions

Meter designation

Nominal voltage, V

Nominal (max) current, A

Accuracy class for active/reactive energy

Communication interface

Mercury 230 AR-XX C(R) of direct and transformer connection

ÀR-00 Ñ(R) 3*57,7/100 5(7,5) 0,5S / 1,0 CAN èëè
RS485
ÀR-01 Ñ(R) 3*220/380 5(50) 1,0S /2,0 CAN èëè
RS485
ÀR-02 Ñ(R) 3*220/380 10(100) 1,0S / 2,0 CAN èëè
RS485
ÀR-03 Ñ(R) 3*220/380 5(7,5) 0,5S / 1,0 CAN èëè
RS485

Mercury 230 AR-XX CL of direct and transformer connection with built-in PLC modem

ÀR-01 ÑL 3*220/380 5(50) 1,0S /2,0 CAN,
PLC-ìîäåì
ÀR-02 ÑL 3*220/380 10(100) 1,0S /2,0 CAN,
PLC-ìîäåì
ÀR-03 ÑL 3*220/380 5(7,5) 0,5S / 1,0 CAN,
PLC-ìîäåì

In meter designation:

 

outline drawing