The system of electric energy selling using RFID SMART cards
|
|
|
ENERGY METERS
one-phase, multi-tariff |
|
Mercury 206
E-meters are designed to register active and reactive electric energy in single-phase AC circuits, and capable of operating both as stand-alone and in the structure of automated data collection systems.
Functionalities:
- Measurement, registration, storage, output to LCD and transfer via interfaces of data on registered active and reactive electric energy as follows:
- Energy with accrued total under each tariff ;
- Energy with accrued total by sum of tariffs ;
- Energy at the beginning of each of 12 last months under each tariff ;
- Energy at the beginning of each of 12 last months by sum of tariffs;
- Availability of the built-in tariff-rater with characteristics as follows:
- Number of tariffs - 4;
- Number of tariff zones within a day - 8;
- Number of day types - 8 ;
- Number of seasons в - 12;
- Measurement, output to LCD and transfer via interfaces of power line parameters as follows: :
- Instantaneous values of active and reactive power and fixed maximums;
- Effective values of phase current and voltage and their maximums ;
- Power line frequency
- Setting active power and energy limits and load shedding at overlimit or by operator's command. Control is performed in two ways:
- Abuse signal delivery to the meter pulse output ;
- Direct management of electric energy supply through the built-in relay (for meters with index «О» in reference designation)).
- Measurement and storage of half-hour power cuts of active energy (power profile). Archive storage depth before overwriting makes 31 days.
- Availability of Event log (circular by 64 records for each event) which fixes data as follows:
- The meter On/Off time
- The meter opening / closing time
- Time, date and a parametrization code.
|
Construction features:
|
- Control of indication
modes through оптопорт.
- Load shed built-in relay |
 |
|
| Technical Specifications |
- Current sensor is a shunt (insensible magnetic field exposure registering constant component) in phase circuit;
- Availability of digital interfaces: optical port in any modification; optional RS485 (CAN), PLC-I;
- Internal or outside power of interface RS485 (CAN);
- Multipurpose pulse output for telemetry, verifications and load shedding management;
- Built-in load shedding relay at current 60А;
- Electronic seal;
- Terminal block with self-expanding terminal of power circuits chains;
- Fastening to a rack .
|
| Документация и ПО
|
| |
Meters display in LCD information as follows: |
- Number of the current tariff
- Energy consumption value for each kind from the operation beginning under each tariff and by all tariffs sum
- Current value of active power in load in kW or kVar
- Current values of current and voltage
- Energy consumption value from the operation beginning on the first day of each of the last 12 months under each tariff and by all tariffs sum
- Time of tariff zones switching
- Current time and date
- Operating time from start-up
- Battery operating time
|
Energy meter with PLС-modem in basic mode transmits uninterruptedly on power line the following data on consumed energy with increasing total without tenth parts kW*h: |
- Total from the moment of indication reset on tariffs sum provided that energy meter is programmed into one-tariff mode;
- Total from the moment of indication reset on current tariff provided that energy meter is programmed into multi-tariff mode;
|
Energy meters provide programming and reading by external computer through optikal interface or RS485(CAN) of the following values: |
| Values |
Programming |
Reading |
| Value of consumed energy from the commencement of operation on each tariff and total on all tariffs in kWh; |
|
+ |
| Value of consumed energy on the first date of each from the previous 11 months on each tariff and total on all tariffs; |
|
+ |
| Individual address; |
+ |
+ |
| Group address; |
+ |
+ |
| Tariff timetable and holiday timetable; |
+ |
+ |
| Current time (hours, minutes, seconds); |
+ |
+ |
| Date (date, month, year); |
+ |
+ |
| Permission flag of transition from “summer” time to “winter” time and reverse; |
+ |
+ |
| Reading of load instant power; |
|
+ |
| Permission flag of time correction by energy meter keys; |
+ |
+ |
| Transmission ratio of pulse output; |
|
+ |
| Exchange rate; |
+ |
+ |
| Number of functioning tariffs; |
+ |
+ |
| Power limit; |
+ |
+ |
| Energy limit; |
+ |
+ |
| Parameters |
Values |
Accuracy class for
- active energy
- reactive energy |
1,0
2,0 |
| Nominal voltage, V |
230 |
| Nominal (max) current, A |
5(60); 5(80); 10(100) |
Maximum current within 10 ms, А
- for Imax=60 А
- for Imax=80 А
- for Imax=100 А |
1800
2400
3000 |
Sensitivity for measuring, А
- for Inom=5А
- for Inom=10 А |
0,020
0,040 |
Active / total power consumption of each parallel circuit, W/V*А not over
- for meters with outside power
- for meters with internal power
- for meters index «L» |
1,2 / 8
2,5/7
1,5/24 |
| Full power, consumed by current circuit, not over V*A |
0,5 |
| Exchange speed, bit/s:
- through interface CAN and RS-485;
- through optikal port;
|
300, 600, 1200, 2400, 4800, 9600
9600 |
| Transmission ratio output, imp/kW,[ imp/kVAr]:
of basic
of verification |
5000
10000 |
Data security at power interruptions, years
- permanent data
- on-line data |
40 10 |
| Data protection |
Metrology factors password access protection and memory hardware protection |
| Temperature range, °С |
от - 45 до +70 |
| Mean time between failures, hours |
220000 |
| Non-failure operation, hours |
7000 |
| Service life, years |
30 |
| Calibration period, years |
10 |
| Weight, kg |
Not over 0,6 |
| Dimensions (LxWxH), mm |
154*105*72 |
| Manufacturer’s warranty, years |
3 |
|
|
| Meter designations:: |
|
Mercury 206 PR(C) LSNO
Mercury – meter trade name
206 - meter series
P - profil of capacity
R - RS485 interface
C - CAN interface
L - PLC-I modem
S - внутренне питание интерфейса
N - электронная пломба
O - встроенное реле
Примечание- Отсутствие символа в наименовании счётчика свидетельствует об отсутствии соответствующей функции. |
| Meter designations: |
|
Mercury 203.2T R(F,C,L,G) Z K(O) B H
Mercury – meter trade name
203 - meter series
2 - electric energy display unit - LCD
Т- inner tariff-rater
R (F,C,L,G) - interface №1, in particular:
R - RS485 interface
F - RF (RF interface) GSM modem
C - CAN interface
L - PLC modem
G - GSM modem
Z - tariff switching by means of external management unit;
К(О)- load management, in particular:
К - through external disconnection management unit output;
О - through relay inside meter;
В - LCD backlight
Н - two current sensors
Missing symbol in meter denomination stands for the relevant function unavailability. |
|

|
|