ELECTRICITY METERS
one-phase, multi-tariff
|
 |
Mercury 205.2Ò FION
Electricity meters are designed for commercial registration of active energy in one-phase AC circuits and operate both autonomously and as a part of AMM.
Functionalities:
- Measurement, registration, storage, output to LCD display and transmission through interfaces data as follows:
- energy with accrued total under each tariff;
- energy with accrued total by tariffs sum;
- energy by the beginning of each of previous 11 months;
- energy by the beginning of each of previous 11 months by tariffs sum;
- The internal meter tariff rater of specifications as follows:
- tariffs - 4;
- tariff zones within 24 hours - 8;
- tariff zones within 24 hours - 8 ;
- seasons - 12;
- Measurement, output to LCD display and transmission through interfaces power mains parameters as follows:
- active power instantaneous values and fixed peak;
- phase current and voltage actual values and their peaks;
- mains frequency
- Consumer power load can be switched off thought a built-in relay fitted into display unit. Power load switching-off can be carried out in three cases::
- A command received via radio interface;
- Power limit preset in meter was exceeded;
- Energy limit preset in meter was exceeded.
- Event log (ringed, 64 records per each event) to fix:
- meter switching on/off time
- device opening/closing time;
- parameterization date;
|
Construction features:
The meter structurally consists of two units – power transducer (below) and display unit (top). The power transducer is placed on external wires of a power line; this prevents possibility of unauthorized energy consumption by some customers. There is remote communication between power transducer and display unit which is conducted via radio interface.
Display unit is fitted with a built-in relay for switching-off consumer power load. |
| |
 |
|
| Technical Specifications |
- Current sensor –current transformer;
- Built-in interfaces – optical port;
- Interfaces – optical port and RF;
- Load shed built-in relay at 60À current;
- LCD backlight;
- Electronic seal.
|
| Documentation
|
| |
Data displayed on LCD: |
- Current tariff number (in multi-tariff mode);
- Energy consumption value in one-tariff mode, kW*h;
- Energy consumption value from putting in operation under each tariff and sum under all tariffs, kW*h;
- Energy consumption value from putting in operation on the first date of the current month and each of previous 11 months under each tariff and by all tariffs sum, kW*h;
- Supply voltage, V;
- Load current, A;
- Load active power (with a sign), kW;
- Power factor;
- Power limit;
- Energy limit, kW*h;
- Response time to power limit excess;
- Control indication of energy limit excess;
- Relay switching-off indication;
- Power value when switching-off occurred;
- Error codes;
- Current time and date;
- Power transducer network number;
- Network address;
- Meters reverse switching-on indication.
|
Data exchange via radio and optical interface |
Parameter |
Programming |
Reading |
• value of consumed active energy; |
|
|
- current value from indications reset per each tariff and per tariffs total; |
|
+ |
- at the beginning of current month per each tariff and per tariffs total; |
|
+ |
- at the beginning of each 11 previous month per each tariff and per tariffs total; |
|
+ |
|
• passwords of the first (consumer) and the second (seller) level of data access |
+ |
|
|
• parameters of the built-in clock: |
- current time and date; |
+ |
+ |
- authorization/prohibition of automated seasonal time switching; |
+ |
+ |
- time switching to «summer» and «winter» time at automated setting of seasonal time; |
+ |
+ |
|
• parameters of rater: |
- rater modes (single-tariff\multi-tariff) |
+ |
+ |
- number of current tariff; |
|
+ |
- tariff schedule; |
+ |
+ |
- public holidays calendar; |
+ |
+ |
|
• mains parameters 230V: |
- power; |
|
+ |
- voltage; |
|
+ |
- power factor; |
|
+ |
- current; |
|
+ |
- mains frequency; |
|
+ |
|
• meter individual parameters: |
- mains address; |
+ |
+ |
- serial number; |
|
+ |
- manufacturing date; |
|
+ |
- meter location; |
+ |
+ |
- accuracy class by active energy; |
|
+ |
- indication parameters; |
+ |
+ |
- Software version; |
|
+ |
|
• control parameters for excess of preset limits of active power and forward direction energy: |
- authorization/prohibition of control for excess of power limit; |
+ |
+ |
- value of preset power limit; |
+ |
+ |
- response time on excess of power limit; |
+ |
+ |
- sign of excess of power limit |
|
+ |
- authorization/prohibition of control for excess of energy limit; |
+ |
+ |
- value of preset energy limit separately for each of four tariffs; |
+ |
+ |
- sign of load switching-of |
|
+ |
- impulse output mode; |
+ |
+ |
|
• event log (ringed for 10 records):
- meter switching on/off time;
- time before/after current time correction;
- time of beginning/ending of power limit excess
- tariff schedule correction time;
- public holiday calendar correction time;
- stored energy registers reset time;
- time of energy limit excess per each tariff;
- parameters correction control time for power limit excess;
- parameters correction control time for energy limit excess;
- devices opening/closing time; |
|
+ |
|
• service information: |
|
|
- meter self-diagnostic status word; |
|
+ |
- recorded data; |
+ |
+ |
-Connected power transducer serial number; |
+ |
+ |
|
|
+ |
| Parameter denomination |
Value |
| Accuracy class for active energy measurement
|
1,0 |
| Nominal (max) current, A |
230 |
| Íîìèíàëüíûé (ìàêñ) òîê, À |
5(60) |
Maximum current within 0,5ms, À
- for Ibas=5À
|
1800 |
Starting current, (sensitivity), À
- for Ibas=5À
|
0,020 |
| Active / full power consumed by display unit voltage path, W/VA, not over |
3 / 6 |
| Active / full power consumed by power sensor
voltage path, W/VA, not over |
2 / 4 |
| Gross power consumed by current circuit no more than, V*A |
0,5 |
| Number of tariffs |
4 |
| Number of tariff seasons (months) |
12 |
| Data rate, bit/second:
- via radio interface;
- via optical port;
|
9600
9600 |
|
Gear ratio of the main/verification output, imp/kW:
|
10000
|
Data security at power shortage, years
- permanent information
- operating information |
40 10 |
| Data protection |
Password and hardware protection of memory metrological coefficients |
| Temperature range, °Ñ |
îò - 40 äî +55 |
| Mean time between failures, |
90000 |
| Mean time between failures, hours |
9000 |
| Error-free operation, hours |
24 |
| Life span, years |
10 |
Dust-, water-proof protection rating
- power transducer
- display unit |
IP 54
IP 51 |
Weight, not over, kg
- power transducer
- display unit |
0,38
0,90 |
Dimensions (length, width, height), mm
- power transducer
- display unit |
112 õ 101,5 õ 90
206 õ 131 õ 73,5 |
| Manufacturer’s warranty period, years |
3 |
|
|
| Meter designations: |
|
Mercury 205.2T FION
Mercury – meter trade mark
205 - meter series
2 - unit to display electric energy – LCD
Ò- inner tariffrater
FION - functions
F - RF (radio interface 2,4 GHZ)
I - optical port
O - load shed by means of built-in relay
N - electronic seal
Missing symbol in meter denomination stands for the relevant function unavailability. |
Display unit

Power transducer


|
|